MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS
(Residential Fire, Residential Burglary, Commercial Burglary)
The NetworX NX-8E panel is necessary to initiate Residential and Commercial installations.
At least one compatible keypad is needed for all applications.
At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the AD10-12 bell and
Grade A bell housing shall be used.
Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
A minimum of two (2) keypads is required for Home Health applications and each keypad must be set to a unique address.
The wireless devices are only UL listed for residential applications.
The DACT shall be enabled for all commercial burglary applications.
STANDBY TIME TOTAL AUXILIARY
CURRENT
STANDBY BATTERY
CAPACITY
ALARM CURRENT
24 hours
1.9 Amps 51 AH 600 mA
1.25 Amps 34 AH 1 Amp
600 mA 17 AH 1 Amp
48 hours
900 mA 51 AH 1 Amp
600 mA 34 AH 1 Amp
300 mA 17 AH 1 Amp
72 hours
600 mA 51 AH 1 Amp
400 mA 34 AH 1 Amp
200 mA 17 AH 1 Amp
Calculations based on three 17-Amp batteries.